Vent-Axia and Duco Fault Codes: Full List by Model

Every fault code, warning and status light for Vent-Axia and Duco ventilation units, by manufacturer and model, with what each one means and what to check. Taken from the manufacturers’ service documentation and kept up to date in our service app.

Short answer: on a Vent-Axia Sentinel Kinetic, 01 means the supply fan has stopped, 02 the extract fan and 03 both fans (01 + 02); 08 and 16 are temperature sensors and 32 the wired remote, and codes add up when several faults happen at once. On an Econiq or current Kinetic Advance, F codes stop the unit, W codes are warnings and N codes are reminders. Duco shows codes as three numbers, such as 1.4.1, in the Duco Installation App and Network Tool.

By Lucas Koc, NZEB ventilation technician · Updated October 2026

On this page

Vent-Axia fault codes

Find the model and stock reference on the label on the unit. Codes differ between ranges, so check the range before you read the table.

Sentinel Kinetic B, BH, Plus, High Flow and FH

Codes add up when several faults happen at once: 03 = 01 + 02, 24 = 08 + 16. A code shows once the fault has been present for 3 minutes.

CodeWhat it meansWhat to check
01Supply fan faultSupply motor not turning. Check the impeller for blockages and the 4-pin motor control and 3-pin power connectors; if sound, replace the supply motor assembly. Parts: 497812 / 417026.
02Extract fan faultExtract motor not turning. Check the impeller and casing for debris and the internal motor cabling; if sound, replace the extract motor assembly. Parts: 497810 / 417028.
03Supply + extract fan faultBoth fans offline (01 + 02). Check mains input voltage, inspect the main control PCBA for damage and check wiring harness continuity. Parts: PCBA 497808.
08Temperature sensor T1Supply duct thermistor disconnected or out of range. Check its connection to the main board; replace the sensor. Parts: 497814.
16Temperature sensor T2Extract air thermistor fault. Check the T2 connections on the PCBA; replace the sensor leads & cable kit. Parts: 497814.
32Wired remote control failureMain board lost the wired remote. Inspect the RJ11 plugs and the cable run, check for interference, or replace the control board/remote.
Room too coldRoom too cold — fan offIndoor temperature below 5 °C (e.g. heating failure): fans stop to avoid drawing in cold air. The unit runs 2 minutes every hour to probe and resumes above 5 °C. Codes show after a fault has been present for 3 minutes; several faults add up (03 = 01 + 02).

Kinetic Advance (older firmware)

Two lists, and each adds up on its own: F codes are faults, W codes are warnings. Example: F 05 = F 01 + F 04.

F codes: faults

CodeWhat it meansWhat to check
F 01Left fan faultMotor locked or disconnected.
F 02Right fan faultMotor locked or disconnected.
F 04Left thermistor faultT2/T3 left sensors.
F 08Right thermistor faultT1/T4 right sensors.
F 16Left centre thermistor faultCheck the sensor and its connection.
F 32Right centre thermistor faultCheck the sensor and its connection.
F 64Left centre temp/humidity sensor faultCheck the sensor and its connection.
F 128Right centre temp/humidity sensor faultCheck the sensor and its connection.

W codes: warnings

CodeWhat it meansWhat to check
W 1Left flow sensor faultyConstant volume limited.
W 2Right flow sensor faultyConstant volume limited.
W 4Left filter sensor faultyFilter indicator reverts to a timer.
W 8Right filter sensor faultyFilter indicator reverts to a timer.
W 16Supply duct over-pressureCheck for blocked or crushed supply ducting and closed valves.
W 32Extract duct over-pressureCheck for blocked or crushed extract ducting and closed valves.
W 64Integrated preheater faulty or disconnectedCheck the preheater supply and connection.

Econiq S, M, L and current Kinetic Advance

F codes stop the unit. W codes are warnings while it keeps running. N codes are reminders.

F codes: the unit stops

CodeWhat it meansWhat to check
F-01Faulty intake temperature sensorInvalid reading; the unit stops because frost protection depends on it. Replace the sensor assembly.
F-02Faulty extract temperature sensorInvalid reading; the unit stops to protect the heat recovery cell from freezing. Replace the sensor assembly.
F-03Faulty supply fanTacho reads zero RPM with power applied. Check the fan harness and impeller rotation; replace the fan motor assembly.
F-04Faulty extract fanTacho reads zero RPM with power applied. Check wiring and plug, clean the impeller, or replace the fan.
F-07Preheater stuck onSafety fault: isolate mains power immediately. Check the preheater supply, solid-state relays and temperature cut-outs; replace the preheater PCBA.
F-08Supply air too coldSupply air at or below +5 °C. Check handing (LH/RH), summer bypass position, heat recovery cell efficiency, and that the house heating works.
F-32HMI comms lostDisplay not receiving from the mainboard. Check the comms harness and RJ45/patch connections and the mainboard power LED; replace HMI or mainboard.

W codes: warnings, the unit keeps running

CodeWhat it meansWhat to check
W-01Faulty supply temperature sensorHeat recovery efficiency figure disabled. Replace the sensor. Clears after the fix and a power cycle.
W-02Faulty exhaust temperature sensorConstant volume and condensation detection affected. Replace the sensor. Clears after the fix and a power cycle.
W-03Preheater temperaturePreheater sensor error or thermal cut-out tripped. Check the manual-reset thermal switch and airflow across the element. Clears after the fix and a power cycle.
W-04Faulty intake RH sensorIndication only, ventilation unaffected. Replace if needed. Clears after the fix and a power cycle.
W-05Faulty extract RH sensorHumidity auto-boost unavailable. Replace the RH sensor. Clears after the fix and a power cycle.
W-06Faulty supply flow sensorConstant volume unavailable; fan runs at fixed speed %. Replace the sensor. Clears after the fix and a power cycle.
W-07Faulty extract flow sensorConstant volume unavailable; fan runs at fixed speed %. Replace the sensor. Clears after the fix and a power cycle.
W-08Faulty filter sensor 1Filter life reverts to a timer. Replace the pressure sensor.
W-09Faulty filter sensor 2Filter life reverts to a timer. Replace the pressure sensor.
W-10Excessive system pressureFans at max duty, target flow not reached. Check crushed ducts, closed fire dampers, blocked external grilles, dirty filters. Clears after the fix and a power cycle.
W-11Preheater trippedThermal cut-out tripped. Check the manual-reset thermal switch and airflow across the element. Clears after the fix and a power cycle.
W-12Filters overdueTimer expired or filters heavily clogged. Clean or replace the filters and reset the filter timer. Clears automatically once resolved.
W-13Machine overdue for serviceService timer expired. Wash the heat exchanger, flush the condensate drain, clean the fans, reset the service timer in the engineer menu. Clears automatically once resolved.
W-14Networked sensor/device lostA CO2/temp/RH/PIR sensor stopped reporting. Replace batteries, check wireless range or the RS485 bus. Clears automatically once resolved.
W-15BMS offlineCheck Modbus RJ45/terminal wiring, address and speed (default 115200/8/N/1). Clears automatically once resolved.
W-16Supply fan Modbus offlinePower figures become estimates. Check motor connection pins and comms wires. Clears automatically once resolved.
W-17Extract fan Modbus offlinePower figures become estimates. Check motor connection pins and comms wires. Clears automatically once resolved.
W-18Bypass / cell issueUnusual efficiency reading. Check the summer bypass actuator, cell alignment and seals. Clears automatically once resolved.
W-19Preheater IO offlineAuxiliary preheater module lost. Check the auxiliary board wiring and power. Clears automatically once resolved.
W-20Cooling unit offlineCool-Flow top module lost; cooling disabled. Check the control cable between base unit and top module. Clears after the fix and a power cycle.
W-21Cooling unit overheatingCompressor overheating; fans go to max. Check filters and the cooling airflow path, or service the refrigeration unit.

N codes: reminders

CodeWhat it meansWhat to check
N-01Filters due soonFilter timer within 30 days of expiry. Inspect filters, order replacements.
N-02Service due soonAnnual service approaching. Schedule maintenance (heat exchanger, condensate trap).
N-03Networked sensor/device offlineWireless node temporarily offline. Check batteries or RF path before it becomes W-14.
N-04Cooling suspendedPressure trip, overheat protection or isolated power. Wait 15 min; check the top module isolator.
N-05Cooling ineffectiveNo temperature drop across the evaporator. Check refrigerant charge and compressor — F-Gas certified technician.

Multivent H and MEV range

Switch the unit off and on again first. If the code comes back, the fault is real.

CodeWhat it meansWhat to check
F01Control fault — failed start-up checkPower off and on again; if it persists replace the control PCBA.
F02Motor fault — no RPMCheck the impeller for blockages and internal motor wiring; replace the motor. (Standard MVDC-MS/H models have no RPM feedback.).
F03Humidity/temp sensor — no valueCheck the sensor ribbon cable is seated; replace the internal sensor module (contact tech support for the part).
F04CO2 sensor — no valueCheck wiring between main board and sensor; replace the sensor if needed.
F05RF/RS485 temp or humidity sensor offlineCheck sensor power (battery if wireless) and re-pair it (Multivent manual p. 10).
F06RF/RS485 CO2 sensor offlineCheck sensor mains/battery power and re-pair it (Multivent manual p. 10).
F074-way speed switch (SSU) offlineCheck the controller power; reconnect or re-pair the switch.
F08Alarm interface module (AIM) offline/triggeredCheck the alarm system state and the harness between HMI/main board and AIM.

Start-up light flashes (Econiq and Advance)

Count the red flashes when the unit powers up. The HMI board is the controller; the mainboard is inside the unit.

HMI board (controller)

CodeWhat it meansWhat to check
1 flashRNG failedHMI board self-test failure.
2 flashesFlash chip (DS-45DB081E) init failedHMI board self-test failure.
3 flashesStorage — flash read/write errorHMI board self-test failure.
4 flashesLCD driver (UC1677) failedHMI board self-test failure.
5 flashesTouch driver (CAP1298) failureHMI board self-test failure.
6 flashesBuilt-in temp/humidity sensor (SHT3x) errorHMI board self-test failure.
7 flashesESP32 sync timeoutHMI board self-test failure.
8 flashesRF868 / wireless auto-tune failedHMI board self-test failure.
9 flashesDisplay app module errorHMI board self-test failure.

Mainboard (inside the unit)

CodeWhat it meansWhat to check
1 flashRNG failedMainboard self-test failure.
2 flashesReal-time clock init failedMainboard self-test failure.
3 flashesEEPROM error (reserved)Mainboard self-test failure.
4 flashesFlash chip (DS-45DB081E) failureMainboard self-test failure.
5 flashesStorage — flash read/write errorMainboard self-test failure.
6 flashesExternal RAM (FM24V01A) failureMainboard self-test failure.
7 flashesVentilation engine failed to startMainboard self-test failure.
8 flashesApplication module init errorMainboard self-test failure.
9 flashesModbus bus init failureMainboard self-test failure.

WiFi controller light (Econiq and Advance)

The light on the WiFi controller shows its connection state.

CodeWhat it meansWhat to check
Solid whiteIdle — paired and connectedNormal operation.
Flashing whiteApp pairing modeWait for the phone app to pair (started by holding Menu for 3 s).
Slow red flashWiFi connection errorCannot reach the router. Reconfigure in AP mode via the app with the correct SSID and key.
Fast red flashFactory reset confirmedRe-pair the HMI and sensors.
Solid light blueBootloader modeShould not appear. Isolate power 30 s and restore; if it persists contact tech support.
Solid purpleFirmware updateWait for it to finish — do not power off.
Solid redLost the mainboardCheck the internal connector cables and power-cycle the MVHR.
Slow red/green flashWiFi board faultReplace the WiFi controller board if a power cycle does not clear it.

Duco error codes

Duco units report errors to the Duco Installation App and the Duco Network Tool. The DucoBox Energy also lists them on its own display.

All DucoBox units

Codes shown in the Duco Installation App and the Duco Network Tool, and on the DucoBox Energy display under INFO → ERROR LIST.

Faults

CodeWhat it meansWhat to check
1.4.1No response from the extractor fanCheck or replace the fan.
3.1.3The temperature sensor of the ODA (supply air from outside to the unit) cannot be readCheck or replace the sensor.
3.1.5The temperature sensor of the ODA (supply air from outside to the unit) is short-circuitedCheck or replace the sensor.
3.1.6The temperature sensor of the ODA (supply air from outside to the unit) has a bad connectionCheck or replace the sensor.
4.1.3The temperature sensor of the ETA (extract air from the house to the unit) cannot be readCheck or replace the sensor.
4.1.5The temperature sensor of the ETA (extract air from the house to the unit) is short-circuitedCheck or replace the sensor.
4.1.6The temperature sensor of the ETA (extract air from the house to the unit) has a bad connectionCheck or replace the sensor.
6.1.3The temperature sensor of the EHA (extract air from the unit to the outside) cannot be readCheck or replace the sensor.
6.1.5The temperature sensor of the EHA (extract air from the unit to the outside) is short-circuitedCheck or replace the sensor.
6.1.6The temperature sensor of the EHA (extract air from the unit to the outside) has a bad connectionCheck or replace the sensor.
16.1.3The pressure sensor for the extract air cannot be readCheck or replace the sensor.
28.4.1No response from the supply fanCheck or replace the fan.
29.1.3The pressure sensor for the supply air cannot be readCheck or replace the sensor.
30.1.3The temperature sensor of the SUP (supply air from the unit to the house) cannot be readCheck or replace the sensor.
30.1.5The temperature sensor of the SUP (supply air from the unit to the house) is short-circuitedCheck or replace the sensor.
30.1.6The temperature sensor of the SUP (supply air from the unit to the house) has a bad connectionCheck or replace the sensor.
33.10.1Outdoor temperature too low, ventilation is switched off permanentlyRestart the DucoBox later.
35.17.1The value of the temperature sensor is too lowCheck or replace the sensor.
35.17.2The value of the temperature sensor is too highCheck or replace the sensor.
35.17.3The value of the temperature sensor cannot be readCheck or replace the sensor.
36.24.1The connection to the weather station is lostCheck the connection.
36.24.2The connection to the outdoor temperature sensor is lostCheck the connection.
36.24.3The connection to the motor of the DucoGrille Close 105 is lostCheck or replace the motor.
36.24.6The connection to the Duco ExtensionHub is lostCheck or replace the Duco ExtensionHub.
37.17.1The value of the CO2 sensor is too lowCheck or replace the sensor.
37.17.2The value of the CO2 sensor is too highCheck or replace the sensor.
37.17.3The value of the CO2 sensor cannot be readCheck or replace the sensor.
40.17.1The value of the humidity sensor is too lowCheck or replace the sensor.
40.17.2The value of the humidity sensor is too highCheck or replace the sensor.
40.17.3The value of the humidity sensor cannot be readCheck or replace the sensor.
42.22.1The number of connected valves is too highThe maximum number is stated in the manual. DucoBox Energy: See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium.
42.22.2The number of connected valves is too lowThe minimum number is 2. DucoBox Energy: See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium.
42.22.3The number of connected control valves is too highThe maximum number is 11.
42.22.4The number of connected control valves is too lowThe minimum number is 2.
42.22.5The number of connected CO2 control valves is too highThe maximum number is 7.
53.28.1The motor is locked by a manual action
53.28.2The motor does not respond to manual actionCheck the communication of the paired user controller.
53.28.3The motor cannot be controlled automatically due to missing dataCheck the installation.
54.29.1The connection to the motor is lostCheck or replace the motor.
54.29.2The motor reports an errorCheck the installation.
54.29.3The desired position of the motor cannot be reachedCheck or replace the motor.
56.31.1An error occurred with a Duco RF componentCheck or replace the component.
56.31.2An error occurred with a Duco Wired componentCheck or replace the component.

Warnings

CodeWhat it meansWhat to check
31.19.1The filters are dirtyReplace the filters.
32.1.1Outdoor temperature too low, ventilation is switched off for 8 hours
43.23.1The adjustment has not yet been done or has failedDo the adjustment (again). DucoBox Energy: See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium.
43.23.2The desired flow rate cannot be achievedCheck the entire installation. DucoBox Energy: See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium.
43.23.11The requested configuration is not correct: the sum of the supply flow rate is greater than the maximum allowed flow rateDo the adjustment again.
43.23.12The calibration is interrupted by a manual action on the displayDo the adjustment again.
43.23.13An error occurred while calculating the resistanceCheck the installation and do the adjustment again.
43.23.14An error occurred during calibrationCheck the installation and do the adjustment again.
43.23.15The adjustment has not yet been done or has failedDo the adjustment (again).
43.23.16The adjustment is interrupted via the Duco Installation App or by an API callDo the adjustment again.
43.23.17The adjustment is interrupted by a manual action via the DNT toolDo the adjustment again.
43.23.18The adjustment is interrupted by activating ‘installer mode’Do the adjustment again.
43.23.19A timeout occurredDo the adjustment again.
43.23.20The prepared configuration contains errors. Too many or too few multi-zone control valves are connected to the ventilation systemCheck the installation and do the adjustment again.
43.23.21The calibration is interrupted due to missing data from the pressure sensorCheck or replace the sensor.
44.6.1There is no connection to the pre-heaterCheck the connection. DucoBox Energy: See installation manual DB Energy Comfort (Plus) or installation manual DB Energy Premium.
46.1.3The outdoor temperature is not availableCheck the connection and the paired sensors.
47.1.3Wind speed is not availableCheck the connection and the paired sensors.
48.1.3Wind direction is not availableCheck the connection and the paired sensors.
49.1.3The light incidence is not availableCheck the connection and the paired sensors.
50.1.3Precipitation is not availableCheck the connection and the paired sensors.
51.26.1The motor of the DucoGrille Close has gone out of its operating rangeCheck or replace the motor.
51.26.2The motor of the DucoGrille Close 105 cannot move due to mechanical overloadCheck the motor for obstructions and the mechanical end-stops.
51.26.4The connection to the motor of the DucoGrille Close 105 is lostCheck the connection.
51.26.5The gear of the motor of the DucoGrille Close 105 has come loose or is freeCheck that the push button is not pressed or replace the motor.
51.26.6An internal activity is in progress, preventing the motor from operating in normal modeDe-energise the DucoGrille Close 105 and start the system again.
55.30.1The temperature of the outdoor temperature sensor cannot be readCheck or replace the sensor.
57.32.1An error occurred in the control of the ventilative coolingCheck the installation.
58.32.1An error occurred in the control of the solar shadingCheck the installation.
60.34.1The value of the temperature sensor of the DucoGrille Close 105 is too highCheck or replace the sensor.
60.34.2The value of the temperature sensor of the DucoGrille Close 105 is too lowCheck or replace the sensor.
60.34.3The value of the temperature sensor of the DucoGrille Close 105 has been too low for at least 1 hourCheck or replace the sensor.
60.34.4The value of the temperature sensor of the DucoGrille Close 105 has been too low for at least 1 dayCheck or replace the sensor.
60.34.5The value of the temperature sensor of the DucoGrille Close 105 has been too low for at least 1 weekCheck or replace the sensor.
61.35.1The prepared configuration contains errorsCheck the configuration.
61.35.2The prepared configuration contains errors. One or more components are not linked to a groupCheck the configuration.
61.35.3The prepared configuration contains errors. One or more components are linked to more than one groupCheck the configuration.
62.36.1The current time is not set. As a result, certain functionalities are not availableSet the time.

Information

CodeWhat it meansWhat to check
No error codeThe DucoBox is live but does not respondCheck or replace the circuit board.
52.27.1Weather protection is activated by rain
52.27.2Weather protection is activated by wind
52.27.3The weather station is not recording any dataCheck the installation.
52.27.4Weather protection is activated by wind and rain
52.27.5The value of the temperature sensor has been constant for a long timeCheck or replace the sensor.
52.27.6Weather protection is activated by external logic
52.27.7The weather protection of a group to which this component belongs, is activated

DucoBox Energy only

These codes appear only on the DucoBox Energy (Comfort, Comfort Plus and Premium).

CodeWhat it meansWhat to check
3.1.1ODA (outdoor air to the unit) temperature sensor value is too lowCheck and/or replace the temperature sensor.
3.1.2ODA (outdoor air to the unit) temperature sensor value is too highCheck and/or replace the temperature sensor.
3.1.4ODA (outdoor air to the unit) temperature sensor has been measuring the same temperature for a long timeCheck and/or replace the temperature sensor.
4.1.1ETA (extract air from the house to the unit) temperature sensor value is too lowCheck and/or replace the temperature sensor.
4.1.2ETA (extract air from the house to the unit) temperature sensor value is too highCheck and/or replace the temperature sensor.
4.1.4ETA (extract air from the house to the unit) temperature sensor has been measuring the same temperature for a long timeCheck and/or replace the temperature sensor.
6.1.1EHA (exhaust air from the unit to the outside) temperature sensor value is too lowCheck and/or replace the temperature sensor.
6.1.2EHA (exhaust air from the unit to the outside) temperature sensor value is too highCheck and/or replace the temperature sensor.
6.1.4EHA (exhaust air from the unit to the outside) temperature sensor has been measuring the same temperature for a long timeCheck and/or replace the temperature sensor.
16.1.1Extract air pressure sensor value is too lowCheck and/or replace the pressure sensor.
16.1.2Extract air pressure sensor value is too highCheck and/or replace the pressure sensor.
16.1.4The extract air pressure sensor has been measuring the same value for a long timeCheck and/or replace the pressure sensor.
16.1.5The extract air pressure sensor is short-circuitedCheck and/or replace the pressure sensor.
16.1.6The extract air pressure sensor has a bad connectionCheck and/or replace the pressure sensor.
29.1.1The supply air pressure sensor is too lowCheck and/or replace the pressure sensor.
29.1.2The supply air pressure sensor is too highCheck and/or replace the pressure sensor.
29.1.4The supply air pressure sensor has been measuring the same value for a long timeCheck and/or replace the pressure sensor.
29.1.5The supply air pressure sensor is short-circuitedCheck and/or replace the pressure sensor.
29.1.6The supply air pressure sensor has a bad connectionCheck and/or replace the pressure sensor.
30.1.1SUP (supply air from the unit to the house) temperature sensor value is too lowCheck and/or replace the temperature sensor.
30.1.2SUP (supply air from the unit to the house) temperature sensor value is too highCheck and/or replace the temperature sensor.
30.1.4SUP (supply air from the unit to the house) temperature sensor has been measuring the same temperature for a long timeCheck and/or replace the temperature sensor.
32.10.1Outdoor temperature too low – ventilation is switched off for 8h
44.6.2A Duco Pre-Heater is connected to the DucoBoxGo to settings to configure it.

Self-test codes on the DucoBox Focus and IQ display

Shown in the display menu under SelfTst. The first characters are the node number of the component with the error; the code after # is the error.

CodeError
#0CO2 error
#1RH error
#2Temperature error
#3Low battery
#4Fan error
#5Motor error
#6Communication error
#7Clima strip error

“Check Filter” message that will not reset

This is a reminder, not a fault code. If it comes back straight after a reset, the usual causes are:

  • Filters fitted the wrong way round, or the wrong grade
  • A faulty filter timer
  • A blocked airflow path
  • Drifted pressure sensors (Kinetic Advance SX)

Step by step: how to reset the Vent-Axia filter message and change the filters.

What a repair costs

Typical prices in Ireland. The final cost depends on the model, access to the unit and the condition of the ducting.

RepairTypical price
Diagnostic visit€120–€150
Fan motor (Kinetic codes 01 and 02)€250–€350 per fan
Temperature or humidity sensor€90–€160
Controller or wiring€150–€220
Summer bypass actuator€250–€360
Condensate drain correction€80–€180

Code still showing?

Switch the unit off at the isolator before opening it. Fan, fuse and circuit board faults need a technician. We find the fault, quote the repair and fix it: book a Vent-Axia repair, call us on 057 851 1416 (answered straight away), or send us a message.

Questions

What does code 03 mean on a Vent-Axia Kinetic?

Both fans have stopped. Kinetic codes add up, and 03 is 01 (supply fan) plus 02 (extract fan). Check the mains supply first; if both fans are still off, the main circuit board is the usual cause.

Can I reset a Vent-Axia fault code myself?

You can switch the unit off at the isolator and back on. If the same code comes back, the fault is real and needs to be found.

Is it safe to leave the unit running with a fault code?

With 01, 02 or 03 one or both fans have stopped, so the house is not being ventilated and moisture builds up quickly. Book a repair within days, not weeks.

Where do I find Duco error codes?

In the Duco Installation App or the Duco Network Tool, and on the DucoBox Energy display under INFO → ERROR LIST. The DucoBox Focus and IQ display also show self-test codes under SelfTst.

Do older units get repaired or replaced?

It depends on the fault and the age of the unit. After the diagnostic visit you get a price for the repair and, when a replacement makes more sense, a price for that too, before any work starts.